HW211

Power Cable

25KV/35KV UL Type MV-105, 105°C
Single Conductor, Shielded
EPR Insulation, PVC Jacket
25KV 133%, 35KV 100% Insulation Level
Copper Conductor

Catalog Number Size AWG/kcmil No. of Strands Insulation Thickness Mils Jacket Thickness Mils Insulation Diameter Inch Overall Diameter Inch Net Weight Lbs/Mft
HW211 10101 1/0 19 345 80 1.11 1.39 1160
HW211 20101 2/0 19 345 80 1.15 1.44 1290
HW211 30101 3/0 19 345 80 1.2 1.49 1445
HW211 40101 4/0 19 345 80 1.26 1.53 1635
HW211 25001 250 37 345 80 1.34 1.59 1805
HW211 35001 350 37 345 80 1.43 1.69 2205
HW211 50001 500 37 345 110 1.56 1.9 2920
HW211 75001 750 61 345 110 1.75 2.09 3895
HW211 10001 1000 61 345 110 1.9 2.24 4840
Application:

For use in power circuits up to 35KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:

Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:

Ethylene propylene rubber (EPR) per ICEA S-97-682.

Shield:

Uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682.

Jacket:

Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072.

Flame Tests:

IEEE 383 70,000 BTU/hr flame test – CT-rated material.

Additional Standards:
Note:

CT ratings are available on sizes 1/0AWG and larger.