HW107 |
||
Instrumentation Cable |
||
600 Volt UL Type TC, 90°C |
For use in instrumentation and process control applications where protection from electrostatic interference is required. UL listed as Type PLTC and ITC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 600 volts. May be used in NEC Class 1, Division 2 hazardous locations. UL approved for NEC continuous operation at 75ºC in wet locations, 90ºC in dry locations, 130ºC for emergency overland conditions, and 250ºC for short circuit locations.
7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.
Flame-retardant PVC per UL Standard 83 for Type THHN or THWN-2 wire.
Clear nylon per UL Standard 83 for Type THHN or THWN wire.
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.
Sunlight-resistant PVC per UL Standard 1277. A ripcord is applied longitudinally under the jacket to facilitate stripping.
UL 1581 70,000 BTU/hr flame test