ANNEX B : Application Information for Ampacity Calculation

Tables B. 310.1 and B. 310.3

PDF Version | Close Window

Table B. 310.1 Ampacities of Two or Three Insulated Conductors, Rated 0 Through 2000 Volts, Within an Overall Covering (Multiconductor Cable), in Raceway in Free Air Based on Ambient Air Temperature of 30° C (86° F)

(AWG or kcmil) Temperature Rating of Conductor. (AWG or kcmil)
60°C
(140°F)
75°C
(167°F)
90°C
(194°F)
60°C
(140°F)
75°C
(167°F)
90°C
(194°F)
Types TW, UF Types RHW, THHW, THW, THWN, XHHW, ZW Types THHN, THHW, THW-2, THWN-2, RHH, RWH-2, USE-2, XHHW, XHHW-2, ZW-2 Type TW Types RHW, THHW, THW, THWN, XHHW Types RHW, THHW, THW, THWN, RHH, RWH-2, USE-2, XHHW, XHHW-2, ZW-2
COPPER ALUMINUM OR COPPER-CLAD ALUMINUM
14 16* 18* 21* 14
12 20* 24* 27* 16* 18* 21* 12
10 27* 33* 36* 21* 25* 28* 10
8 36 43 48 28 33 37 8
6 48 58 65 38 45 51 6
4 66 79 89 51 61 69 4
3 76 90 102 59 70 79 3
2 88 105 119 69 83 93 2
1 102 121 137 80 95 106 1
1/0 121 145 163 94 113 127 1/0
2/0 138 166 186 108 129 146 2/0
3/0 158 189 214 124 147 167 3/0
4/0 187 223 253 147 176 197 4/0
250 205 245 276 160 192 217 250
300 234 281 317 185 221 250 300
350 255 305 345 202 242 273 350
400 274 328 371 218 261 295 400
500 315 378 427 254 303 342 500
600 343 413 468 279 335 378 600
700 376 452 514 310 371 420 700
750 387 466 529 321 384 435 750
800 397 479 543 331 397 450 800
900 415 500 570 350 421 477 900
1000 448 542 617 382 460 521 1000
Correction Factors
Ambient Temp. (°C) For ambient temperatures other than 30°C (86°F), multiply the ampacities shown above by the appropriate factor shown below. Ambient Temp. (°F)
21-25 1.08 1.05 1.04 1.08 1.05 1.04 70-77
26-30 1.00 1.00 1.00 1.00 1.00 1.00 79-86
31-35 0.91 0.94 0.96 0.91 0.94 0.96 88-95
36-40 0.82 0.88 0.91 0.82 0.88 0.91 97- 104
41-45 0.71 0.82 0.87 0.71 0.82 0.87 106-113
46-50 0.58 0.75 0.82 0.58 0.75 0.82 115-122
51-55 0.41 0.67 0.76 0.41 0.67 0.76 124-131
56-60 0.58 0.71 0.58 0.71 133-140
61-70 0.33 0.58 0.33 0.58 142-158
71-80 0.41 0.41 160-176

*Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for these conductor types shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper; or 15 amperes for 12 AWG and 25 AWG amperes for 10 AWG aluminum and copper-clad aluminum.

Table B. 310.3 Ampacities of Multiconductor Cables with Not More Than Three Insulated Conductors, Rated 0 Through 2000 Volts, in Free Air Based on Ambient Air Temperature of 40° C (104° F) (For Types TC, MC, MI, UF, and USE Cables)

(AWG or kcmil) Temperature Rating of Conductor. (AWG or kcmil)
60°C
(140°F)
75°C
(167°F)
85°C
(185°F)
90°C
(194°F)
60°C
(140°F)
75°C
(167°F)
85°C
(185°F)
90°C
(194°F)
COPPER ALUMINUM OR COPPER-CLAD ALUMINUM
18 11* 18
16 16* 16
14 18* 21* 24* 25* 14
12 21* 28* 30* 32* 18* 21* 24* 25* 12
10 28* 36* 41* 43* 21* 28* 30* 32* 10
8 39 50 56 59 30 39 44 46 8
6 52 68 75 79 41 53 59 61 6
4 69 89 100 104 54 70 78 81 4
3 81 104 116 121 63 81 91 95 3
2 92 118 132 138 72 92 103 108 2
1 107 138 154 161 84 108 120 126 1
1/0 124 160 178 186 97 125 139 145 1/0
2/0 143 184 206 215 111 144 160 168 2/0
3/0 165 213 238 249 129 166 185 194 3/0
4/0 190 245 274 287 149 192 214 224 4/0
250 212 274 305 320 166 214 239 250 250
300 237 306 341 357 186 240 268 280 300
350 261 337 377 394 205 265 296 309 350
400 281 363 406 425 222 287 317 334 400
500 321 416 465 487 255 330 368 385 500
600 354 459 513 538 284 368 410 429 600
700 387 502 562 589 306 405 462 473 700
750 404 523 586 615 328 424 473 495 750
800 415 539 604 633 339 439 490 513 800
900 438 570 639 670 362 469 514 548 900
1000 461 601 674 707 385 499 558 584 1000
Correction Factors
Ambient Temp. (°C) For ambient temperatures other than 40°C (104°F), multiply the ampacities shown above by the appropriate factor shown below. Ambient Temp. (°F)
21-25 1.32 1.20 1.15 1.14 1.32 1.20 1.15 1.14 70-77
26-30 1.22 1.13 1.11 1.10 1.22 1.13 1.11 1.10 79-86
31-35 1.12 1.07 1.05 1.05 1.12 1.07 1.05 1.05 88-95
36-40 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 97-104
41-45 0.87 0.93 0.94 0.95 0.87 0.93 0.94 0.95 106-113
46-50 0.71 0.85 0.88 0.89 0.71 0.85 0.88 0.89 115-122
51-55 0.50 0.76 0.82 0.84 0.50 0.76 0.82 0.84 124-131
56-60 0.65 0.75 0.77 0.65 0.75 0.77 133-140
61-70 0.38 0.58 0.63 0.38 0.58 0.63 142-158
71-80 0.33 0.44 0.33 0.44 160-176

*Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for these conductor types shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper; or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper-clad aluminum

Back to Annex B