ARTICLE 310: Conductors for General Wiring

NEC Table 310.85

PDF Version | Close Window

Table 310.85 Ampacities of Three Triplexed Single Insulated Copper Conductors Directly Buried in Earth Based on Ambient Earth Temperature of 20°C (68°F), Arrangement per Figure 310.60, 100 Percent Load Factor, Thermal Resistance (RHO) of 90, Conductor Temperatures 90°C (194°F) and 105°C (221°F)

Conductor Size (AWG or kcmil) Temperature Rating of Conductor
2001 - 5000 Volts Ampacity 5001 - 35,000 Volts Ampacity
90°C (194°F) Type MV-90 105°C (221°F) Type MV-105 90°C (194°F) Type MV-90 105°C (221°F) Type MV-105
One Circuit, Three Conductors (See Figure 310.60, Detail 7.)
8 90 95
6 120 130 115 120
4 150 165 150 160
2 195 205 190 205
1 225 240 215 230
1/0 255 270 245 260
2/0 290 310 275 295
3/0 330 360 315 340
4/0 375 405 360 385
250 410 445 390 410
350 490 580 470 505
500 590 635 565 605
750 725 780 685 740
1000 825 885 770 830
Two Circuits, Six Conductors (See Figure 310.60, Detail 8.)
8 85 90
6 110 115 105 115
4 140 150 140 150
2 180 195 175 190
1 205 220 200 215
1/0 235 250 225 240
2/0 265 285 255 275
3/0 300 320 290 315
4/0 340 365 325 350
250 370 395 355 380
350 445 480 425 455
500 535 575 510 545
750 650 700 615 660
1000 740 795 690 745