Share This Page

HW110: 600V Multiple Pairs or Triads - FR-EP, CPE, I/S & O/S

Application

Superior flame-retardant cable for use in instrumentation and process control applications in caustic environments where protection from electrostatic interference is required. UL listed as Type TC and approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays and direct burial in circuits not exceeding 600 volts. May be installed at temperatures as low as -35°C and used in NEC Class 1, Division 2 hazardous locations. UL approved for NEC continuous operation at 90°C in wet and dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors

  • 7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8

Insulation

  • Flame-retardant ethylene propylene rubber (FR-EP) per ICEA S-82-552

Individual Shield

  • Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire

Overall Shield

  • Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire

Jacket

  • Sunlight-resistant chlorinated polyethylene (CPE) per ICEA S-82-552 and UL Standard 1277. A ripcord is applied longitudinally under the jacket to facilitate stripping

Color Code

  • Pairs: black and white with printed numbers on one conductor
  • Available upon request: black and red pairs with printed number

Additional Standards

  • NEC Type TC per articles 336, 392 and 501, and Class 1 circuits per NEC article 725
  • NEMA WC-55
  • UL Type TC-ER Rated for Exposed Run

Flame Tests

  • IEEE 383 (70,000 BTU/hr) Flame Test
  • IEEE 1202 (70,000 BTU/hr)
  • UL 1277 (70,000 BTU/hr) Flame Test
  • ICEA T-29-520 (210,000 BTU/hr) Flame Test
  • CSA FT4 Flame Test

Browse HW110: 600V Multiple Pairs or Triads - FR-EP, CPE, I/S & O/S Products

  • Products
  • >
  • Products
  • >
  • HW110: 600V Multiple Pairs or Triads - FREP, CPE, I/S & O/S

HW110: 600V Multiple Pairs or Triads - FREP, CPE, I/S & O/S

Superior flame-retardant cable for use in instrumentation and process control applications in caustic environments where protection from electrostatic interference is required. UL listed as Type TC and approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays and direct burial in circuits not exceeding 600 volts. May be installed at temperatures as low as -35°C and used in NEC Class 1, Division 2 hazardous locations. UL approved for NEC continuous operation at 90°C in wet and dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Loading products...

HWC also specializes in hard-to-find specialty items. The HWC team is always concerned with filling customers' orders as properly and efficiently as possible. And if it's not in stock, HWC will get it- no problem! Get A Quote

Ask Us A Question Or Leave Us A Comment

Industries We Serve

With over 30,000 products sold annually, Houston Wire & Cable provides its customers with knowledgeable market and product application experts, standard same-day shipments, 99.99% order accuracy and on-time delivery, and 24/7/365 service.

Choose...